Salta al contenuto principale
Passa alla visualizzazione normale.

MARIA LUISA DI SILVESTRE

An analysis methodology to evaluate the contribution to electrical security given by bare buried conductors in a system of intertied earthing grids

Abstract

The paper presents an analysis methodology for a single-line-to-ground fault, occurring at a secondary MV/LV substation in a power network formed by a HV7MV station, feeding, through a MV tri-phase cable line, N MV/LV substations whose earth electrodes are interconnected by bare buried conductors. Preliminary explayning the methodology, earth buried conductors are studied in their double function of earth electrodes and connection elements between earthing grids, both in absence and in presence of other interfering conductors. Subsequently is analyzed, with a distributed parameters approach, the system constituted by an earth buried conductor and a MV tri-phase cable line. The equations that describe system behaviour are solved with the decoupling method of Modal Analysis. The proposed methodology allows to determinate the currents injected in the ground by the buried conductor and by the earth electrodes of the substations, as a consequence of an earth fault, whichever is the faulty substation. A numerical example clarifies the presented methodology. © 2003 IEEE.